Performance Chart

The Performance Chart below are divided into two sections to help you evaluate the overall performance of the systems. The System Performance Criteria are the most important to consider because they represent the performance in a typical installation.

SYSTEM PERFORMANCE CRITERIA (Tested on Actual Understructure)
Panel
U/S
SYSTEM
WEIGHT
(lbs/ft²)
STATIC LOADS
ROLLING LOADS
IMPACT
LOADS(lbs)
Design
Loads*(lbs)
Safety
Factors*(min 2.0)
10
Passes(lbs)
10,000
Passes(lbs)
All Steel 1250
Bolted Stringer
7.0
1250
PASS
500
500
150

*For more information on design load download the Design Load Technical Bulletin. All other tests are conducted under CISCA’s recommended test procedures for access floors.

Download PDF

Product Guide

All Steel System Specifications