Performance Chart

The Performance Charts below are divided into two sections to help you evaluate the overall performance of the systems. The System Performance Criteria are the most important to consider because they represent the performance in a typical installation.

FF1250 SYSTEM PERFORMANCE CRITERIA (Tested on Actual Understructure)

Panel U/S SYSTEM WEIGHT
(lbs/ft²)
STATIC LOADS ROLLING LOADS IMPACT LOADS
(lbs)
Design Loads*
(lbs)
Safety Factors*
(min 2.0)

10 Passes
(lbs)
10,000 Passes
(lbs)
Solid Panels Bolted Stringer/
Stringerless/
Cornerlock
6.5 1250 2.0 1000 1000 150
Perf Panels Bolted Stringer/
Stringerless/
Cornerlock
6.25 1250 2.0 1000 1000 150
Grates Bolted Stringer/
Stringerless/
Cornerlock
7.25 1250 2.0 1000 1000 150

 

FF3000 SYSTEM PERFORMANCE CRITERIA (Tested on Actual Understructure)

Panel U/S SYSTEM WEIGHT
(lbs/ft²)
STATIC LOADS ROLLING LOADS IMPACT LOADS
(lbs)
Design Loads*
(lbs)
Safety Factors*
(min 2.0)

10 Passes
(lbs)
10,000 Passes
(lbs)
Solid Panels Bolted Stringer/
Stringerless/
Cornerlock
7.60 2250 2.0 2000 2000 200
Perf Panels Bolted Stringer/
Stringerless/
Cornerlock
7.40 2000 2.0 1500 2000 100

 

*For more information on design load download the Design Load Technical Bulletin.  All other tests are conducted under CISCA’s recommended test procedures for access floors.